Bailey Controls SLC CLC
Home Our Company Our Customers Career Opportunities Contact Us
 

Boiler control integrators

   MicroMod Home » Application Solutions » Boiler Control » Burner Management

Burner Management Systems for Boiler Control

BurnerPAK is a series of microprocessor-based, single-burner control systems designed in accordance with the NFPA 85 safety standard to provide the correct burner sequence, ignition and flame monitoring protection on automatically ignited oil, gas, and combination fuel burners. In conjunction with limit and operating controls, a BurnerPAK burner management system provides control and monitoring of the startup and shutdown sequence of burners and related equipment, monitors the operation of the equipment at all times, and initiates safe shutdown procedure on detection of an unsafe operating condition. The system also provides current operating status and lockout information in the event of a safety shutdown.

BurnerPAK burner management systems provide hardware-independent, configurable times for purge, post-purge, flame failure response time (FFRT), and flame stabilization as well as maximum travel time for the air actuator and FD fan startup time. All setup screens are password protected for security.

MicroMod can also provide BMS systems for multiple burners and co-firing oil & gas burners.

 Burner Management System, Drum Pressure Control

Data Sheet

BurnerPAK-1 is a self-contained standalone controller that provides both burner management system and drum pressure control, and is ideal for small (100-300 HP) package boilers. An analog input is provided for the steam pressure signal. The controller compares the signal to an operator-entered setpoint and generates an output signal to the jackshaft actuator. The integral display panel provides operation and monitoring of the drum pressure control loop as well as indication of burner sequence, status and MFT alarm information. Setup of the drum pressure loop and the burner sequence times is done through the display keypad.

 Burner Management System with Enhanced Alarming

Data Sheet

BurnerPAK-3 is a standalone Burner Management System for use with any combustion control system. In addition to control and indication of the burner sequence, BurnerPAK-3 provides enhanced alarming and identification of the specific limit in the operating control circuit or running interlock circuit which caused the burner shutdown. System runtime information, English or Spanish language displays and Ethernet connectivity are all features of BurnerPAK-3.

  

Click on a display to view a larger image

 

In addition to BurnerPAK pre-engineered systems, MicroMod offers BMS systems for multi-burner and co-fired boilers. Contact us at for more information.

Combustion Control
Oil & Gas
Solid & Biofuels
Drum Level & Feedwater
Burner Management
Balance-of-Plant
Touchscreens & Consoles
Tools & Resources
Application Data
Case Histories
Efficiency & Payback Calculator


If you know which SteamPAK package you need, click here

For help selecting a package, or if the standard SteamPAK systems don't fit your needs, click here

 

 
  Top of page

MicroMod Automation • 75 Town Centre Drive Rochester, NY 14623, USA

Phone: 585-321-9200 • Fax: 585-321-9291 •
In the U.S. call toll free 1-800-480-1975